PCU is a Solar Power Conditioning Unit (PCU) which uses Solar energy (primary) and also the power from grid (secondary), to charge the batteries as well as to feed to connected load. Since usage of power from grid is secondary, grid power is only used when solar energy is not present and battery voltage level reduces to a certain level. Grid power is also needed when solar power is reduced to a certain level and battery voltage is reduced to a certain level. PCU uses an advanced technology named MPPT (Maximum Power Point Tracking) to extract maximum power from the solar panel. The overall system is compact and easy to install.
Available Range:1 KVA , 2 KVA , 3 KVA , 5 KVA , 6 KVA , 7.5 KVA , 10 KVA.
Key features:
- Longer battery life
- Extensive electronic protections
- Utilizes maximum power available from the panel
- Computer interface (Optional)
- LCD display with Energy Meter and Data Logging (Optional)
Protection:
Short ckt on o/p terminals; Reverse polarity on DC i/p terminals; overload; over temperature; panel reverse.
Built-in indicators: System On, Inverter On, SP charging, Battery Low / High, Mains low / High, Overload
Application:
Indoor only.
PARAMETERS | UNITS | 1KVA / 24V | 1KVA / 48V | 2KVA / 48V | 3KVA / 48V | 5KVA / 96V | 2KVA / 24V |
Nominal Battery Voltage | V | 24 | 48 | 48 | 48 | 96 | 24 |
Input voltage range | VDC | 22-30 | 43.2 -60.0 | 43.2 -60.0 | 43.2 – 60.0 | 86.4 – 120 | 22-30 |
Output Voltage | VAC | 215-225 | |||||
Inverter efficiency at rated resistive load | % | 85-90 | |||||
Output frequency | Hz | 50 | |||||
Total Harmonic Distortion (THD) | % | <3 | |||||
Nominal Power | W | 800 | 800 | 1600 | 2400 | 4000 | 1600 |
Maximum Input current | A (DC) | 52 | 28 | 56 | 84.26 | 73.5 | 90 |
Maximum load current | A (AC) | 4.5 | 4.5 | 9 | 13.5 | 18 | 7.3 |
Power factor | 0.8 | ||||||
Self consumption | mA | 200 | 300 | 200 | 200 | 300 | 300 |
Power saving / Sleep mode | Yes | ||||||
battery deep discharge protection | Load disconnect (LVD) at: | 21.6V | 43.2V | 43.2V | 43.2V | 86.4V | 21.6V |
Operating temperature | *C | 0 to 55 | |||||
AC charging | Yes | ||||||
Temperature compensation | No | ||||||
Audible noise produced by inverter | dB | <60 | |||||
Ingress Protection | IP21 |
Alpha PCU Technical Specification (User Configurable):
Solar charge controller | IGBT Based |
Solar charge logic | MPPT |
Solar panel rating | Up to 100% (More optional) |
Maximum open ckt voltage | 45V x No. of Battery |
Panel type(cell) / (For each battery) | 36/60/72 |
LCD | 4 Line LCD |
Energy meter | YES |
30 Days data logging | YES |
Display | Batt. volt,Batt charging current,battery dscharging current,Batt charging cumulative power(+AH),batt |
USB | YES |
Ethernet/ SNMP | Optional |
Battery type selection | YES |
Parameter configuration/calibration | YES |
Grid charging enable/disable | YES |
No load shut down E/D | YES |
Lightening protection | YES |
Zero Change over time | No |
Grid Power Factor Correction | No |
Application | Commercial |
Grid & Solar Sharing | Battery Charging |
Beta PCU Technical Specification [Pre-configured Inverter Mode]
PARAMETERS | VALUES |
Solar charge controller | MOSFET Based |
Solar charge logic | MPPT |
Solar panel rating | Up to 100% (More optional) |
Maximum open ckt voltage | 22V x No. of Battery |
Panel type(cell) / (For each battery) | 36 cell |
LCD | 2 Line LCD |
Energy meter | No |
30 Days data logging | No |
Display | Batt voltage,Battery charging current,Batt discharging current,output voltage,output load percentage |
USB | Optional |
Ethernet/ SNMP | No |
Battery type selection | No |
Parameter configuration/calibration | No |
Grid charging enable/disable | No |
No load shut down E/D | No |
Lightening protection | Yes |
Zero Change over time | No |
Grid Power Factor Correction | No |
Application | Commercial |
Grid & Solar Sharing | Battery charging |
Solar Online PCU Technical Specification [UPS mode]
PARAMETERS | VALUES |
Solar charge controller | IGBT Based |
Solar charge logic | MPPT |
Solar panel rating | Up to 100% (More optional) |
Maximum open ckt voltage | 45V x No. of Battery |
Panel type(cell) / (For each battery) | 36/60/72 |
LCD | 4 Line LCD |
Energy meter | YES |
30 Days data logging | YES |
Display | Batt. volt,Batt charging current,battery dscharging current,Batt charging cumulative power(+AH),batt |
USB | Yes |
Ethernet/ SNMP | Optional |
Battery type selection | Yes |
Parameter configuration/calibration | Yes |
Grid charging enable/disable | No |
No load shut down E/D | YES |
Lightening protection | YES |
Zero Change over time | YES |
Grid Power Factor Correction | YES |
Application | IT |
Grid & Solar Sharing | Load and battery charging |
Home PCU- Sunpack (Hybrid home UPS):
Sunpack is a solar hybrid inverter which utilizes solar power as primary source and Grid power as secondary source to charge the batteries. Sunpack is designed to give you the maximum advantage from the sun and reduces your electricity cost. As Sunpack and solar panel do not produce harmful gases and residue, it helps in keeping the environment clean and healthy / eco-friendly.
Available Range: 100VA to 3KVA( 36V/ 48V)
Key Features:
- Sine Wave Output
- Preference to Solar Power over Grid power
- Can operate without Solar Panel also
- Any battery option
- Extensive electronic protections
- Affordable and easy to install
- Battery Health For Longer Life
Protections:
Panel / Battery Reverse; No Reverse Current Flow from Battery to Solar Array; Load Short Circuit
Built- in Indicator: Panel ON, Overload, Charging On, Battery Low
PARAMETERS | DESCRIPTIONS | UNITS | 1075 (12V) | 1675 (24V) |
Operation Logic | First Priority | Solar charging | ||
Second priority | Solar + Grid charging (if PV low) | |||
Third priority | Grid charging | |||
INPUT | Voltage | V | 100-290 (+/- 5V) / 170-260 (+/- 5V) | 100-290 (+/- 5V) / 170-260 (+/- 5V) |
CHARGE CONTROLLER | Technology | Switch | ||
Precise Control | Micro Controller Based Design | |||
Peak Open-Circuit Voltage | V | PVOC <22.5V | PVOC < 45V | |
Charging Mode (Float) | V | 13.2 / 13.8 | 26.4 / 27.6 | |
Charging Mode (Boost) | V | 14.3 / 14.5 | 28.6 / 29.0 | |
Charging Current | A | 7-Oct | 7-Oct | |
Battery low cut | V | 10.0 +/- 0.2V | 10.0 +/- 0.2V | |
No load shut down (optional) | Available (Minimum load sense : 15W) | |||
BATTERY DETAILS | Nominal voltage | V | 12 | 24 |
Type | LMLA / SMF / Tubular | |||
INVERTER SPECIFICATIONS | Output Voltage (AC) | V | 220 ± 5% | |
Output Frequency | Hz | 50 ± 0.05% | ||
Efficiency | % | >80 | ||
Power factor | 0.8 lag | |||
Wave Form type | Sine wave | |||
Battery low alarm | V | 10.4 +/- 0.2V | 20.4 +/- 0.2V | |
PROTECTIONS | Panel / Battery Reverse | Provided through DC fuse | ||
No Reverse Current Flow from Battery to Solar Array | Provided | |||
Load Short Circuit | Shut Down | |||
INDICATIONS | LEDs & BUZZER | Panel ON, Overload, Charging On, Battery Low | ||
OVERLOAD | 101% – 120% | 7 times ON/OFF, then Shut Down | ||
121% – 300% | Output voltage is halved | |||
> 300% | Immediately Shut down | |||
GENERAL | Operating Temperature | °C | 0 to + 40 | |
Storage Temperature | °C | 0 to + 55 | ||
Humidity | % | 0 to 95 | ||
Acoustic Noise | dB | <60 |